StorEdge™ and Smart Energy Firmware Updates

Note: when upgrading the firmware, do not insert SD card when inverter is ON. After upgrade is finished, remove the SD card when inverter is OFF. Do not leave SD card inside.

Version Date October-31-2018


Firmware versions

CPU LG DCDC LG BMS Tesla Powerwall 1
3.2317 4.6 1.4.6.0 2.30.5

 


 


Release Notes

New Features and Enhancements

  1. Support StorEdge solution for backup with a three phase External Disconnection Unit (from Enwitec) in DACH
  2. Added New England region to inverter country list

Firmware File

LG: CPU_3_2317_LG_Dcdc_4_6_BMS_1_4_6_0_October_31_18.bsuf

Tesla Powerwall 1 batteries with battery firmware 2.19 and above:
CPU_3_2317_Tesla_2_30_5_October_31_2018.bsuf

 

Important notes

  1. This version is for StorEdge systems only
  2. Use Firefox or Chrome browsers to download firmware files.
  3. For Tesla batteries with battery firmware version lower than 2.19, contact SolarEdge support
  4. The firmware file can only be loaded to a memory card that meets the specifications listed in the Software Upgrade using SD/MicroSD card application note
  5. Firmware upgrade procedure can be found at:
    1. StorEdge Interface: StorEdge Interface Wiring Guide & On Site Checklist
    2. StorEdge Inverter: StorEdge Inverter Wiring Guide & On Site Checklist

 



Version Date October-11-2018


Firmware versions

CPU LG DCDC LG BMS Tesla Powerwall 1
3.2316 4.6 1.4.6.0 2.30.5

 


 


Release Notes

New Features and Enhancements

  1. StorEdge:
    1. Support StorEdge solution for backup with a single phase External Disconnection Unit (from Enwitec) in Belgium and the Netherlands.
    2. Support Tesla Powerwall 1 batteries with Tesla firmware 2.19 and above. For batteries with a lower battery firmware version, contact SolarEdge support.


Fixed Issues

  1. Improved unlocking of ‘backup over consumption’ to prevent DC from dropping.
  2. Fixed LCD blinking during ‘backup over consumption'.
  3. Support SE-Meter BSUF upgrade.
     

    Important notes

    1. This version is for StorEdge systems only
    2. Use Firefox or Chrome browsers to download firmware files.
    3. The firmware file can only be loaded to a memory card that meets the specifications listed in the Software Upgrade using SD/MicroSD card application note
    4. Firmware upgrade procedure can be found at:
      1. StorEdge Interface: StorEdge Interface Wiring Guide & On Site Checklist
      2. StorEdge Inverter: StorEdge Inverter Wiring Guide & On Site Checklist

         

         

    Version Date April-16-2018


    Firmware versions

    CPU LG DCDC LG BMS
    3.2305 4.6 1.4.6.0

     


     

    Release Notes

    New Features and Enhancements

    1. StorEdge:
      1. Full charge hysteresis for LG batteries changed to 99%
    2. HD-Wave:
      1. SunSpec support - grid frequency measurement resolution updated to 1mHz

     

    Fixed Issues

    1. LG battery sent false energy value when in sleep mode

       

      Important notes

      1. This version is for StorEdge systems only
      2. This version is for systems with LG batteries; For Tesla Powerwall 1 use earlier firmware versions.
      3. Use Firefox or Chrome browsers to download firmware files.
      4. The firmware file can only be loaded to a memory card that meets the specifications listed in the Software Upgrade using SD/MicroSD card application note
      5. Firmware upgrade procedure can be found at:
        1. StorEdge Interface: StorEdge Interface Wiring Guide & On Site Checklist
        2. StorEdge Inverter: StorEdge Inverter Wiring Guide & On Site Checklist
           

      Version Date February-8-2018



      Firmware versions

      CPU LG DCDC LG BMS
      3.2191 4.6 1.4.6.0

       


       

       

      Release Notes

      New Features and Enhancements

      1. StorEdge:

      1. The maximum supported distance between the inverter and the LG battery is 50 meters
      2. Italy: Support CEI 0-21

       

      Important notes

      1. This version is for StorEdge systems only
      2. This version is for systems with LG batteries; For Tesla Powerwall 1 use earlier firmware versions.
      3. Use Firefox or Chrome browsers to download firmware files.
      4. The firmware file can only be loaded to a memory card that meets the specifications listed in the Software Upgrade using SD/MicroSD card application note
      5. Firmware upgrade procedure can be found at:
        1. StorEdge Interface: StorEdge Interface Wiring Guide & On Site Checklist
        2. StorEdge Inverter: StorEdge Inverter Wiring Guide & On Site Checklist


      Version Date November-1-2017



      Firmware versions

      CPU LG DCDC LG BMS Tesla Powerwall 1
      3.2186 4.6 1.4.6.0 2.30.5

       


       

       

      Release Notes

      New Features and Enhancements

      1. StorEdge:
      1. Support of LG Chem batteries with HD-Wave inverters 
      2. Support of StorEdge with Smart Energy
      3. Support Tesla Powerwall 1 for:
        - New installations
        - Existing installations with smart energy

      Note: this is the last supported firmware version for Tesla Powerwall 1.

      2. Smart Energy: 
      1. Improved application/monitoring UI response time (Manual On/Off): Instead of seeing a spinning wheel until the action ends, it responds immediately and the status (On/Off) is reported via the regular telemetries a few seconds later
      2. Support of StorEdge with smart energy devices
      3. Meters: Support of energy meters with Modbus connection earlier firmware versions
       
       
      Fixed Issues
      1. StorEdge: 
      1. Improved Maximize Self-Consumption response time with LG battery
      2. LG Chem battery fault 3 split into:
        i. Fault 3 warning – battery voltage = 480V
        ii. Fault 8 error – battery circuit breaker trip at ~500V

       

      Important notes

      1. Use Firefox or Chrome browsers to download firmware files.
      2. The firmware file can only be loaded to a memory card that meets the specifications listed in the Software Upgrade using SD/MicroSD card application note
      3. When upgrading a system with Powerwall 1 with firmware version lower than 2.19.10, first upgrade to version 2.19.10 (version available on this page) and only then upgrade to the latest FW version.
      4. Firmware upgrade procedure can be found in:
      _________________________________________________________________________________________________________________________________________

       

      Version Date August-13-2017

      Firmware versions

      CPU LG DCDC LG BMS
      3.2171 2.3 1.4.6.0

       


       

       

      Release Notes

      New Features and Enhancements

      1. StorEdge:
      1.1 Support of StorEdge + Home Energy Management (Device Control)
      2. Home Energy management (Device Control): 
      2.1 Added Excess solar power mode
      2.2 Support of StorEdge + Home Energy Management (Device Control)
      3. Meters:
      3.1 Support for three phase revenue grade WND meter (CT setting lock feature)
      3.2 Added inverter production and site production meter types, to distinguish between meters installed at inverter output and on all the site
      3.3 Support for meter measurements at the MV connection point, for delta and WYE MV grids. Under Device Type -> Meter, added:
      i. Topology – WYE/Delta
      ii. PT Scale - potential transformer scale factor, 1-999
      4. Other:
      4.1 Export limitation clustering: for up to 16 buses of up to 32 inverters per bus.
      4.2 Austria: added Q Global Setting and P Global Setting menus under Reactive Power Conf, to comply with TOR D4 requirements. Requires supporting DSP versions.
      4.3 New countries: Belgium Delta, Norway Delta, Netherland MV, Taiwan 220V No N; All new countries require supporting DSP versions.
       
      Fixed Issues
      1. Home Energy Management (Device Control): Smart Save mode enabled also when battery is OFF

        

      Important notes

      1. Use Firefox or Chrome browsers to download firmware files.
      2. The firmware file can only be loaded to a memory card that meets the specifications listed in the Software Upgrade using SD/MicroSD card application note
      3. For Tesla Powerwall 1 use earlier firmware versions.
      4. Firmware upgrade procedure can be found in:
       
      _______________________________________________________________________________________________________________________________________________________________

      Version Date June-08-2017

      Firmware versions

      CPU DSP1 DSP2 LG DCDC LG BMS
      3.2155 1.210.1069 2.52.415 2.3 1.4.6.0

       


       

       

      Release Notes

      New Features and Enhancements
      1.      StorEdge:
      1.1.   Support of LG Chem RESU7H and RESU10H batteries with StorEdge inverter (with Backup mode) and StorEdge Interface SESTI-S1/SESTI-S2 with single phase non-HD-Wave inverters.
       

       

      Important Notes

      1. Use Firefox or Chrome browsers to download firmware files.
      2. The firmware file can only be loaded to a memory card that meets the specifications listed in the Software Upgrade using SD/MicroSD card application note
      3. For Tesla Powerwall 1 use earlier firmware versions.
      4. Firmware upgrade procedure can be found in:
       
      _______________________________________________________________________________________________________________________________________________________________

      Version Date May-22-2017

      Firmware version

      CPU DSP1 DSP2 LG DCDC LG BMS
      3.2150 1.210.1068 2.52.410 2.3 1.4.6.0

       


       

       

      Release Notes

      New Features and Enhancements
      1.      StorEdge:
      1.1.    Support of LG Chem RESU7H and RESU10H batteries with StorEdge Interface SESTI-S1/SESTI-S2 with single phase non-HD-Wave inverters, or StorEdge Inverter.
       

      Known Issues
      1.3.    StorEdge Inverters do not work in Backup mode; next version will support this.

       

       

      ________________________________________________________________________________________________________________________________________________________________

      Version Date May-28-2017
       

      Release Notes

      1.      StorEdge:
      1.1.    Resolved issues: When two batteries are connected to StorEdge Interface SESTI-S2 or to StorEdge Inverter SExxxx-xx2, the system will stop discharging only if both batteries reach minimum SOE (previously discharge stopped as soon as one battery reached minimum SOE).
      2.      Device Control:
      2.1.   Fixed bug which didn’t enable using Smart Save schedule when Maximize Self-Consumption was selected and there was no battery connected.
       

      Firmware version

      CPU DSP1 DSP2 Powerwall 1
      3.2023 1.210.1068 2.52.410 2.30.5

       



       

      Firmware Files

      Notes:
      1. Use Firefox or Chrome browsers to download firmware files.
      2. When upgrading a system with Powerwall 1 with firmware version lower than 2.19.10, first upgrade to version 2.19.10 (version available on this page) and only then upgrade to the latest FW version.

      BATTERY PART NUMBER

      BATTERY SERIAL NUMBER

      FIRMWARE FILE

      1067000-00-B

      T16D

      0006143
      0006229-0006273, 0006579-0006585
      0006587-0006641, 0006726-0006900
      0006923-0007043

       

      T16E

      0007601-0007631, 0007633-0007648
      0007650-0007655, 0007657-0007675

      T16F

      0007676-0007711, 0007713-0007785
      0007796-0007805, 0007827-0007832
      0007834-0007836

      T16F

      0007859-0007904, 0007906-0007957
      0008265-0008267, 0008279-0008304
      0008430-0008442

      Others

       

      1067000-00-C

      T16D

      0006154- 0006158, 0006274-0006577
      0006649, 0006651-0006675
      0006677-0006698, 0006725
      0007097-0007129, 0007138-0007141
      0007146-0007330, 0007332-0007337
      0007339-0007390
       

      T16E

      0007480-0007526, 0007530-0007540
      0007544-0007596, 0007807-0007826

      T16F

      0007847-0007852, 0007856, 0007958
      0007960-0008049, 0008051-0008136
      0008305-0008385, 0008443-0008462
      0008473-0008589, 0009451-0009555
      0009561-0009562, 0009564-0009568
      0009571-0009574, 0009576-0009577
      0009579-0009637, 0009639-0009668

      T16G

      0009798-0009831, 0009833-0009931
      0009937-0009999, 0010000-0010013
      0010023
      0010026-0010033, 0010038-0010068
      0010070, 0010072, 0010074-0010075
      0010082-0010090, 0010093
      0010096-0010097, 0011145-0011156
      0011446-0011464, 0011466, 0011468
      0011471-0011474, 0011481-0011483
      0011485-0011544, 0011559-0011586

      1067000-00-C

      or

      1067000-00-E

      or

      1067000-01-E

      T15K

      0000501, 0000507, 0000610

       

      T15L

      0000804, 0001137, 0001921, 0001924
      0001927, 0002229, 0002467, 0002532
      0002549-0002551, 0002557-0002558
      0002574-0002575, 0002591
      0002595-0002596, 0002598-0002601
      0002603-0002604, 0002641, 0002644
      0002647-0002649, 0002651-0002654
      0002666, 0002671-0002672
      0002674, 0002677, 0002681-0002682
      0002686-0002689, 0002691-0002693
      0002695-0002697, 0002699
      0002707-0002713, 0002715

      T16C

      0005396-0005397, 0005399

      T16G

      0009832, 0009932-0009936
      0010014-0010022, 0010024-0010025
      0010034-0010037, 0010069, 0010071
      0010073, 0010076-0010081
      0010091-0010092, 0010094-0010095
      0010176-0010184, 0010229-0010246
      0010248-0010296, 0010298-0010331
      0010333-0010340, 0010342-0010362
      0010488-0010636, 0010638-0010648
      0010650-0010868, 0010870-0011141
      0011395-0011421, 0011423-0011444
      0011465, 0011467, 0011469-0011470
      0011475, 0011477-0011480
      0011484, 0011545-0011557
      0011596, 0011600-0011602
      0011604-0011630, 0011632
      0011643-0011644, 0011658-0011659
      0011661-0011662, 0011904-0011905

      Others

       

       

       

       

      Version Date March-02-2017


       

      Firmware version

      CPU DSP1 DSP2 TESLA
      3.2016 1.210.1066 2.52.410 2.30.4

       

       

       

      Release Notes

      New Features and Enhancements

      1.      StorEdge:
      1.1.    Support of two Tesla Powerwall 1 batteries for high power (other than Type B+B). Requires StorEdge Inverter/Interface for higher power output.
      1.2.    Two Powerwall 1 batteries when used for high capacity: seamless transition between two batteries during backup
      1.3.    Support Tesla Powerwall 1 heating when battery temp is -20 to 0 °C
      1.4.    For Tesla Powerwall 1 with firmware v2.30.4, dark start (wake up from DC) is:
      ·      Enabled in StorEdge Inverters (with backup)
      ·      Disabled in all other inverters
      1.5.    Charge of “Backup reserved” part of battery, or all battery charge when using “Backup only”, can now be selected between PV only and between PV+AC (default).
      1.6.    StorEdge Inverters: RS485-2 support, including menu display (requires compatible communication board with RS485-2)
      2.      HD-Wave Inverters:
      2.1.    StorEdge support (non-backup)
      2.2.    Improved IR button responsiveness behavior
      3.      Device Control: Support of multiple Smart Save schedules per day
      4.      Other:
      4.1.    New countries: Thailand MEA MV, Thailand PEA MV, China MV, France MV; All new countries require Digital v1.13.818 and above
      4.2.    High frequency telemetry for site info and device control info
       
      Fixes
      1.    Device Control: Import threshold automatically set according to device rated power; removed from device properties menu
      2.    Meters: Fixed Inepro PRO380 parity setting - commissioning menu now sets its to parity = none
       

      Firmware Files

      Note: Use Firefox or Chrome browsers to download firmware files.

      Battery Part Number

      Battery Serial Number

      Firmware File

      1067000-00-B

      T16D

      0006143
      0006229-0006273, 0006579-0006585
      0006587-0006641, 0006726-0006900
      0006923-0007043

      Type B1 batteries

      CPU_3_2016_Tesla_2_30_4_B1_Mar_02_2017.BSUF

      T16E

      0007601-0007631, 0007633-0007648
      0007650-0007655, 0007657-0007675

      T16F

      0007676-0007711, 0007713-0007785
      0007796-0007805, 0007827-0007832
      0007834-0007836

      T16F

      0007859-0007904, 0007906-0007957
      0008265-0008267, 0008279-0008304
      0008430-0008442

      Others

      Type B batteries

      CPU_3_2016_Tesla_2_30_4_B_Mar_02_2017.BSUF

      1067000-00-C

      T16D

      0006154- 0006158, 0006274-0006577
      0006649, 0006651-0006675
      0006677-0006698, 0006725
      0007097-0007129, 0007138-0007141
      0007146-0007330, 0007332-0007337
      0007339-0007390
      Type C batteries

       

      CPU_3_2016_Tesla_2_30_4_C_Mar_02_2017.BSUF

      T16E

      0007480-0007526, 0007530-0007540
      0007544-0007596, 0007807-0007826

      T16F

      0007847-0007852, 0007856, 0007958
      0007960-0008049, 0008051-0008136
      0008305-0008385, 0008443-0008462
      0008473-0008589, 0009451-0009555
      0009561-0009562, 0009564-0009568
      0009571-0009574, 0009576-0009577
      0009579-0009637, 0009639-0009668

      T16G

      0009798-0009831, 0009833-0009931
      0009937-0009999, 0010000-0010013
      0010023
      0010026-0010033, 0010038-0010068
      0010070, 0010072, 0010074-0010075
      0010082-0010090, 0010093
      0010096-0010097, 0011145-0011156
      0011446-0011464, 0011466, 0011468
      0011471-0011474, 0011481-0011483
      0011485-0011544, 0011559-0011586

      1067000-00-C

      or

      1067000-00-E

      or

      1067000-01-E

      T15K

      0000501, 0000507, 0000610

      Type E batteries

      CPU_3_2016_Tesla_2_30_4_E_Mar_02_2017.BSUF

      T15L

      0000804, 0001137, 0001921, 0001924
      0001927, 0002229, 0002467, 0002532
      0002549-0002551, 0002557-0002558
      0002574-0002575, 0002591
      0002595-0002596, 0002598-0002601
      0002603-0002604, 0002641, 0002644
      0002647-0002649, 0002651-0002654
      0002666, 0002671-0002672
      0002674, 0002677, 0002681-0002682
      0002686-0002689, 0002691-0002693
      0002695-0002697, 0002699
      0002707-0002713, 0002715

      T16C

      0005396-0005397, 0005399

      T16G

      0009832, 0009932-0009936
      0010014-0010022, 0010024-0010025
      0010034-0010037, 0010069, 0010071
      0010073, 0010076-0010081
      0010091-0010092, 0010094-0010095
      0010176-0010184, 0010229-0010246
      0010248-0010296, 0010298-0010331
      0010333-0010340, 0010342-0010362
      0010488-0010636, 0010638-0010648
      0010650-0010868, 0010870-0011141
      0011395-0011421, 0011423-0011444
      0011465, 0011467, 0011469-0011470
      0011475, 0011477-0011480
      0011484, 0011545-0011557
      0011596, 0011600-0011602
      0011604-0011630, 0011632
      0011643-0011644, 0011658-0011659
      0011661-0011662, 0011904-0011905

      Others

      Type E1 batteries

      CPU_3_2016_Tesla_2_30_4_E1_Mar_02_2017.BSUF

       

       

       


       

      Version Date December-01-2016

      Firmware version

      CPU DSP1 DSP2 TESLA
      3.1968 1.210.1057 2.52.410 2.19.10

       

       

       

      Release Notes

      New Features and Enhancements
      1 StorEdge:
      1.1 Tesla battery firmware version changed to 2.19.10
      2 Device control:
      2.1 For Device Control with StorEdge systems: Disable Smart Save when system is not in “Maximize Self-consumption” mode
      2.2 Performance improvements when Schedule and Smart Save overlap
      2.3 Monitoring platform support (requires monitoring Device Control support):
      2.3.1 Send status telemetries for every configuration change
      2.3.2 Performance improvements when minimum and maximum on times are the same (Smart Save only)
       
      Fixed Issues
      1 StorEdge: Maximize Self-consumption table no longer corrupted after reset
      2 Device Control: Immersion Heater manual control – mode is now reported correctly
       
      Known Issues
      None

       

      Firmware Files

      Note: Use Firefox or Chrome browsers to download firmware files.

      Battery Part Number

      Battery Serial Number

      Firmware File

      1067000-00-B

      T16D

      0006143
      0006229-0006273
      0006579-0006641
      0006726-0006900
      0006923-0007043

       

      T16E

      0007601-0007675

      T16F

      0007676-0007785
      0007827-0007832
      0007834-0007836

      T16F

      0007859-0007957
      0008265-0008267
      0008279-0008304
      0008430-0008442

      Others

       

      1067000-00-C

      All

       

      1067000-00-E or
      1067000-01-E

      T16G

      0010176-0010184
      0010229-0010331
      0010333-0010636
      0010638-0010648

       

      T16H 0011904 – 0011905

      Others

       


      Firmware for Device Control Only:

      For Device Control only (without StorEdge)   Firmware file: CPU_3_1968_Dec_01_2016.bsuf



       

      For StorEdge with or without Device Control:

      Battery Part Number

      Battery Serial Number

      Firmware File

      1067000-00-B

      T16D


      0006143
      0006229-0006273, 0006579-0006585
      0006587-0006641, 0006726-0006900
      0006923-0007043

      Type B1 batteries

      CPU_3_1968_Tesla_2_19_10_B1_Dec_01_2016.BSUF

      T16E

      0007601-0007631, 0007633-0007648
      0007650-0007655, 0007657-0007675

      T16F

      0007676-0007711, 0007713-0007785
      0007796-0007805, 0007827-0007832
      0007834-0007836

      T16F

      0007859-0007904, 0007906-0007957
      0008265-0008267, 0008279-0008304
      0008430-0008442

      Others

      Type B batteries

      CPU_3_1968_Tesla_2_19_10_B_Dec_01_2016.BSUF

      1067000-00-C

      T16D

      0006154- 0006158, 0006274-0006577
      0006649, 0006651-0006675
      0006677-0006698, 0006725
      0007097-0007129, 0007138-0007141
      0007146-0007330, 0007332-0007337
      0007339-0007390

      Type C batteries

      CPU_3_1968_Tesla_2_19_10_C_Dec_01_2016.BSUF

      T16E

      0007480-0007526, 0007530-0007540
      0007544-0007596, 0007807-0007826

      T16F

      0007847-0007852, 0007856, 0007958
      0007960-0008049, 0008051-0008136
      0008305-0008385, 0008443-0008462
      0008473-0008589, 0009451-0009555
      0009561-0009562, 0009564-0009568
      0009571-0009574, 0009576-0009577
      0009579-0009637, 0009639-0009668

      T16G

      0009798-0009831, 0009833-0009931
      0009937-0009999, 0010000-0010013
      0010023
      0010026-0010033, 0010038-0010068
      0010070, 0010072, 0010074-0010075
      0010082-0010090, 0010093
      0010096-0010097, 0011145-0011156
      0011446-0011464, 0011466, 0011468
      0011471-0011474, 0011481-0011483
      0011485-0011544, 0011559-0011586

      1067000-00-C

      or

      1067000-00-E

      or

      1067000-01-E

      T15K

      0000501, 0000507, 0000610

      Type E batteries

      CPU_3_1968_Tesla_2_19_10_E_Dec_01_2016.BSUF

      T15L

      0000804, 0001137, 0001921, 0001924
      0001927, 0002229, 0002467, 0002532
      0002549-0002551, 0002557-0002558
      0002574-0002575, 0002591
      0002595-0002596, 0002598-0002601
      0002603-0002604, 0002641, 0002644
      0002647-0002649, 0002651-0002654
      0002666, 0002671-0002672
      0002674, 0002677, 0002681-0002682
      0002686-0002689, 0002691-0002693
      0002695-0002697, 0002699
      0002707-0002713, 0002715

      T16C

      0005396-0005397, 0005399

      T16G

      0009832, 0009932-0009936
      0010014-0010022, 0010024-0010025
      0010034-0010037, 0010069, 0010071
      0010073, 0010076-0010081
      0010091-0010092, 0010094-0010095
      0010176-0010184, 0010229-0010246
      0010248-0010296, 0010298-0010331
      0010333-0010340, 0010342-0010362
      0010488-0010636, 0010638-0010648
      0010650-0010868, 0010870-0011141
      0011395-0011421, 0011423-0011444
      0011465, 0011467, 0011469-0011470
      0011475, 0011477-0011480
      0011484, 0011545-0011557
      0011596, 0011600-0011602
      0011604-0011630, 0011632
      0011643-0011644, 0011658-0011659
      0011661-0011662, 0011904-0011905

      Others

      Type E1 batteries

      CPU_3_1968_Tesla_2_19_10_E1_Dec_01_2016.BSUF

       

       

       


       

      Version Date October-19-2016

       

      Firmware versions

      CPU DSP1 DSP2 Tesla
      3.1958 1.210.1054 2.52.410 2.22.6

       

       

       

      Release Notes

       
      New Features and Enhancements
      1 StorEdge:
      1.1 Improved maximize self-consumption response time and accuracy
      2 If inverter shuts down during backup (for example due to high power), when it tries to reconnect the LCD displays “Waking up” and the elapsed time (in sec) from when it tries to reconnect.
      3 Low SOE limit for battery operating range
      3.1 For Tesla batteries with Tesla version 2.22.4 and above: SOE = 4%
      3.2 For Tesla batteries with version lower than 2.22.4: SOE = 6%.
      4 LCD indication of firmware upgrade progress – the following screens are shown in succession (upgrading battery shown only when applicable):
      StorEdge LCD indication
      5 Device Control support
      6 Import/Export Limitation
      6.1 Improved export control response time and accuracy 
      6.2 Zero export failsafe mechanism: when export limitation is set to 0, production stops if there is export for more than 30sec.
      7 Inverter error codes now displayed only in hexadecimal format; previous format removed
      7.1 Refer to inverter installation guide for translation between the two formats
      8 Italy test from LCD; Configuration Tool will no longer be used
      9 Arc detection
      10 Sunspec Protocol
      10.1 Indication if StorEdge system is in backup mode or not (bit 0 in I_Event_1_Vendor register)
      10.2 Support of new error format – hexadecimal (register I_Event_4_Vendor)
      10.3 Support of negative DC current values in the register
      10.4 Improved DC voltage resolution from integers to one decimal place
      10.5 Faster update of meter power measurements – up to 5sec
      10.6 New battery state: no communication with battery (state 7)
      11 Board replacement: param backup (activation parameters – power, country) with SD card instead of using the configuration tool; inverter configurations done after activation are not saved.
       
       
      Fixed Issues
      1 None
       
      Known Issues
      1 None
       

      Firmware Files

       

      Battery Part Number

      Battery Serial Number

      Firmware File

      1067000-00-B

      T16D

      0006143
      0006229-0006273, 0006579-0006585
      0006587-0006641, 0006726-0006900
      0006923-0007043

      Type B1 batteries
       

      T16E

      0007601-0007631, 0007633-0007648
      0007650-0007655, 0007657-0007675

      T16F

      0007676-0007711, 0007713-0007785
      0007796-0007805, 0007827-0007832
      0007834-0007836

      T16F

      0007859-0007904, 0007906-0007957
      0008265-0008267, 0008279-0008304
      0008430-0008442

      Others

      Type B batteries
       

      1067000-00-C

      T16D

      0006154- 0006158, 0006274-0006577
      0006649, 0006651-0006675
      0006677-0006698, 0006725
      0007097-0007129, 0007138-0007141
      0007146-0007330, 0007332-0007337
      0007339-0007390

      Type C batteries
       

      T16E

      0007480-0007526, 0007530-0007540
      0007544-0007596, 0007807-0007826

      T16F

      0007847-0007852, 0007856, 0007958
      0007960-0008049, 0008051-0008136
      0008305-0008385, 0008443-0008462
      0008473-0008589, 0009451-0009555
      0009561-0009562, 0009564-0009568
      0009571-0009574, 0009576-0009577
      0009579-0009637, 0009639-0009668

      T16G

      0009798-0009831, 0009833-0009931
      0009937-0009999, 0010000-0010013
      0010023
      0010026-0010033, 0010038-0010068
      0010070, 0010072, 0010074-0010075
      0010082-0010090, 0010093
      0010096-0010097, 0011145-0011156
      0011446-0011464, 0011466, 0011468
      0011471-0011474, 0011481-0011483
      0011485-0011544, 0011559-0011586
      1067000-00-C
      or
      1067000-00-E
      or
      1067000-01-E

      T15K

      0000501, 0000507, 0000610

      Type E batteries
       

      T15L

      0000804, 0001137, 0001921, 0001924
      0001927, 0002229, 0002467, 0002532
      0002549-0002551, 0002557-0002558
      0002574-0002575, 0002591
      0002595-0002596, 0002598-0002601
      0002603-0002604, 0002641, 0002644
      0002647-0002649, 0002651-0002654
      0002666, 0002671-0002672
      0002674, 0002677, 0002681-0002682
      0002686-0002689, 0002691-0002693
      0002695-0002697, 0002699
      0002707-0002713, 0002715

      T16C

      0005396-0005397, 0005399

      T16G

      0009832, 0009932-0009936
      0010014-0010022, 0010024-0010025
      0010034-0010037, 0010069, 0010071
      0010073, 0010076-0010081
      0010091-0010092, 0010094-0010095
      0010176-0010184, 0010229-0010246
      0010248-0010296, 0010298-0010331
      0010333-0010340, 0010342-0010362
      0010488-0010636, 0010638-0010648
      0010650-0010868, 0010870-0011141
      0011395-0011421, 0011423-0011444
      0011465, 0011467, 0011469-0011470
      0011475, 0011477-0011480
      0011484, 0011545-0011557
      0011596, 0011600-0011602
      0011604-0011630, 0011632
      0011643-0011644, 0011658-0011659
      0011661-0011662, 0011904-0011905

      Others

      Type E1 batteries
       

       

       

       


       

      Version Date August-03-2016

       

      Firmware versions

      CPU DSP1 DSP2 Tesla
      3.1822 1.210.1006 2.52.403 2.19.10
       
       
       
       
       

      Release Notes

      New Features and Enhancements
      1 Support of multiple Tesla battery hardware options (E and E1). Use the table below to identify the appropriate firmware file for updating your battery:

      Battery Part Number

      Battery Serial Number

      Firmware File

      1067000-00-B

      T16D

      0006143
      0006229-0006273
      0006579-0006641
      0006726-0006900
      0006923-0007043

      Firmware package B1: CPU_3_1822 Tesla_2_19_10_B1 Aug 3_2016.bsuf

      T16E

      0007601-0007675

      T16F

      0007676-0007785
      0007827-0007832
      0007834-0007836

      T16F

      0007859-0007957
      0008265-0008267
      0008279-0008304
      0008430-0008442

      Others

      Firmware package B: CPU_3_1822 Tesla_2_19_10_B Aug 3_2016.bsuf

      1067000-00-C

      All

      Firmware package C: CPU_3_1822 Tesla_2_19_10_C Aug 3_2016.bsuf

      1067000-00-E or
      1067000-01-E

      T16G

      0010176-0010184
      0010229-0010331
      0010333-0010636
      0010638-0010648

      Firmware package E: CPU_3_1822 Tesla_2_19_10_E Aug 3_2016.bsuf

      T16H 0011904 – 0011905

      Others

      Firmware package E1: CPU_3_1822 Tesla_2_19_10_E1 Aug 3_2016.bsuf

       
      Fixed Issues
      1 None
       
      Known Issues
      1 None
       

       


       

      Version Date July-25-2016

       

      Firmware files:

      • Type B batteries: CPU_3_1822 Tesla_2_19_10_B July 25_2016.bsuf
      • Type B1 batteries: CPU_3_1822 Tesla_2_19_10_B1 July 25_2016.bsuf
      • Type C batteries: CPU_3_1822 Tesla_2_19_10_C July 25_2016.bsuf
       

      Firmware versions

      CPU DSP1 DSP2 Tesla
      3.1822 1.210.1006 2.52.403 2.19.10
       
       
       
       
       

      Release Notes

      New Features and Enhancements
      1 Support of multiple Tesla battery hardware options – different firmware file per battery type:
      1.1 Type B: batteries with thermal connection terminals
      1.2 Type B1: sub group of type B, identified according to the serial number:
      1.2.1 T16D0006229 - T16D0006273
      1.2.2 T16D0006579 - T16D0006641
      1.2.3 T16D0006726 - T16D0007043
      1.3 Type C: batteries without thermal connection terminals
       
      Fixed Issues
      1 None
       
      Known Issues
      1 None
       

       


       

      Version Date July-22-2016

       

      Firmware file: CPU_3_1822 Tesla_2_19_10_B July 22_2016.bsuf

       

      Firmware versions

      CPU DSP1 DSP2 Tesla
      3.1822 1.210.1006 2.52.403 2.19.10
       
       
       
       
       

      Release Notes

      New Features and Enhancements
      1 None
       
      Fixed Issues
      1 StorEdge:  Battery upgrade script fix
       
      Known Issues
      1 None
       
       

       


       

      Version Date July-13-2016

       

      Firmware file: CPU_3_1822 Tesla_2_19_10 July 13_2016.bsuf

       

      Firmware versions

      CPU DSP1 DSP2 Tesla
      3.1822 1.210.1006 2.52.403 2.19.10
       
       
       
       
       

      Release Notes

      New Features and Enhancements
      1 None
       
      Fixed Issues
      1 StorEdge:  In systems with a ZigBee Home Gateway using Charge/Discharge Profile Programming, the time is now displayed properly on the monitoring portal.
       
      Known Issues
      1 None
       
       

       


       

      Version Date July-6-2016

       

      Firmware file: CPU_3_1820 Tesla_2_19_10 July 7_2016.bsuf

       

      Firmware versions

      CPU DSP1 DSP2 Tesla
      3.1820 1.210.1006 2.52.403 2.19.10
       
       
       
       
       

      Release Notes

      New Features and Enhancements
      1 StorEdge:
      1.1 Inverter max output power in backup mode is set to a battery discharge power equal to the battery max power (3.3kW for the Tesla Battery).
      1.2 Automatic detection of Tesla battery hardware ID.
      1.3 Tesla "low energy recovery mechanism" for battery operation after sleep is now used also in backup mode.
       
       
      Fixed Issues
      1 None
       
      Known Issues
      1 None
       
       

       


       

      Version Date May-18-2016

       

      Firmware file: CPU_3_1810 Tesla_2_19_10 May 18_2016.bsuf

       

      Firmware versions

      CPU DSP1 DSP2 Tesla
      3.1810 1.210.961 2.52.326 2.19.10
       
       
       
       
       

      Release Notes

      New Features and Enhancements
      1 None
       
      Fixed Issues
      1 StorEdge – maximizing self-consumption application improvements
       
      Known Issues
      1 None
       
       

       

      Version Date April-3-2016

       

      Firmware file: CPU_3_1808 Tesla_2_19_8 April_3_2016.bsuf

       

      Firmware versions

      CPU DSP1 DSP2 Tesla
      3.1810 1.210.961 2.52.326 2.19.8
       
       
       
       
       

      Release Notes

      New Features and Enhancements
      1 StorEdge
      1.1 Supports AC coupling with SolarEdge three phase inverters and with non-SolarEdge inverters
      1.2 Supports 2 batteries for additional capacity
      1.3 Supports backup power (with StorEdge Inverter with Backup)
       
      2 Import/Export Limitation
      2.1 Improved limit control accuracy and stability
      2.2 Export limitation with 3rd party generator (for example a non-SolarEdge inverter) with import/export meter: generator production is taken into account when calculating the needed limitation (but it is not controlled by the SolarEdge system)
      2.3 If a production meter is connected at the output of the generator, all calculated (virtual) meters are displayed in the monitoring portal; if such a meter is not connected, export limitation will work properly but only physical meters will be displayed in the portal.
      2.4 Minimum import limitation: production does not start until minimum import is reached; this is equivalent to negative export
       
      3 Meters
      3.1 Support of up to 3 Modbus meters
      3.2 Inepro meter support: InePro PRO1 (1ph meter) / PRO380 (3ph meter) with v1.18 and above: can used for production/consumption/import/export monitoring, and for export limitation
      3.3 New meter type: external production (non-SE) – used for export limitation with 3rd party generator and for AC coupling with non-SolarEdge inverter
       
      4 Optimizer Status Menu: added per-optimizer menus, under each of the main menus (All, Non-Reporting)
      4.1 For non-reporting optimizers the last telem is either that of last telem or 0; if it’s 0 all other fields will display N/A
      4.2 The screen is refreshed every 5 sec
       
      5 Cellular: GSM/CDMA server connection remains open for 1 hour after pairing
       
      6 External control of the inverter AC relays through the Power Reduction Interface of the inverter
       
      7 Italy test from LCD; Configuration Tool will no longer be used
       
      8 Sunspec Protocol
      8.1 3 meter support
      8.2 View meter type
       
      9 SolarEdge Open Protocol:
      9.1 StorEdge control
      9.2 View/set grid protection parameters
       
      10 Modbus over TCP
      10.1 Same Modbus registers as for Modbus over RS485
      10.2 Modbus TCP can be enabled/disabled with LCD button; configuration requires internal buttons
       
      11 Local software upgrade with SD card: SD card can be used multiple times without having to delete the state (not applicable to SE card)
       
      Fixed Issues
      1 StoraEdge
      1.1 Disabling limit control does not affect StorEdge system operation
       
      Known Issues
      1 None
       
       

       

      Version Date Feb-14-2016

       

      Firmware file: CPU_3_1755 Tesla_2_14 Feb_14_2016.bsuf

       

      Firmware versions

      CPU DSP1 DSP2 Tesla
      3.1755 1.210.945 2.52.314 2.14
       
       

       

       

      Release Notes

      New Features and Enhancements
      1 Tesla battery upgrade through the inverter using a micro-SD card
      2 Faster upgrade of a Tesla battery
      3 SunSpec/Modbus reading via TCP connection of up to 3 Modbus meters
      4 SunSpec/Modbus control via TCP connection
       
      Fixed Issues
      1 None
       
      Known Issues
      1 None